Technical Specification | |
No of ways | 4,6 & 8 ways |
Type of installation | Flush / Surface |
Colour / Finish | RAL 7035 semi glossy |
Door Options | Flat Version |
Door Locking option | Comforts slide lock |
Removable Gland Plates | Top & Bottom |
Protection level of distribution boards | Advanced |
Distribution Technique | Insulated straight busbar |
Busbar Rating | 100 A |
Busbar Short Time Withstand | 5 kA for 0.1 sec |
Busbar conditional short circuit | 10 kA |
Incoming | Max 63 A per phase |
Outgoing | Max individual 32 A |
Voltage Rating | 240-415 V AC , 3 Phase / 4 Wire |
Incoming options | 100 A Isolator (4P) & R, Y, B Indicating lights (3P + N) & 100 A RCCB (4P) |
Residual Current Protective Devices options | RCCB or RCBO as incomer (4P) |
Neutral Bar terminal capacity | 25 sq.mm. |
Earthing Bar Terminal Capacity | 25 sq.mm. |
Index of Protection (IP) | IP 4X |
Insulation Voltage | 690V AC |
Frequency | 50 Hz |
Ambient Temperature | -5° C to 40° C |
Distribution Board – Reference standard | IS 8623 ; IS 13032 ; IEC 60439-3 |
Protective Devices – Reference standard | IS/IEC 60947-2 ; IS/IEC 60898 ; IS/IEC 60947-3 |
Residual Current Protective Devices – Reference standard | IS 12640: Part 1 & 2 ; IEC 61008 ; IEC 61009 |
Index of Protection – Reference standard | IS / IEC 60529 |